The personable computer people
Contact our team
Call on 01621 877600 or send us a message

Salicru 6A0EA000009 SPS ADVANCE T 3000VA/2100W 230V Line Interactive UPS, Extended Runtime

£399.00 inc. VAT

In stock

SKU: 6A0EA000009 Categories: ,

Description

Condition
Item is in “USED LIKE NEW CONDITION” will be fully functional but may have SLIGHT signs of use. The original outer packaging will have some cosmetic damage. Sold with full manufacturer’s warranty. VAT invoice provided. 
 REQUIRES EXTENDED BATTERY MODULE AS STANDARD

Technical Specifications
Technology Line-interactive
Format Tower
Input
Rated Voltage 230 V
Voltage Range 100% Load 165 ÷ 290 V
Stabiliser AVR (Buck & Boost)
Rated Frequency 50 / 60 Hz (auto-detection)
Frequency Range ±5 Hz
Auto~Detection Of Frequency Yes
Protection Resettable breaker
Output
Rated Voltage 230 V
Voltage Accuracy (Battery Mode) ±10%
Power (Va/W) 3000 / 2700
Total Harmonic Distortion (THDV) <5%
Waveform (Battery Mode) Pure sine wave
Frequency 50/60 Hz (same as input)
Frequency Accuracy (Battery Mode) ±1 Hz
Compatibility With Apfc Loads Yes (1)
Performance Stabiliser Mode (Avr) >92%
Performance Battery Mode
>80% Admissible overloads in battery mode
110% For 1 Min / >130% Immediate Admissible overloads in-line mode
110% 1Min / 120% Immediate Socket type
IEC C13 + Terminals
No. Of Sockets 4
Battery
Battery Type Pb-Ca sealed, AGM, maintenance-free
Charge Type I/U (constant current/constant voltage)
Recharge Time 4 hours to 90%
Battery Test Automatic on each start-up + manual
Communication
Ports RS-232 / USB (HID)
Intelligent Slot Slot for SNMP/potential-free contacts/ MODBUS
Monitoring Software For Windows, Linux and Mac
Indications
Type LCD + keypad
Values Input and output voltage / % load / % battery / backup
Levels Connected load / overload / battery / low battery
Operating Modes Normal / Stabilisation (AVR) / Battery / Fault
Alarm Battery / low battery / overload / failure
Audible Every 30 s for battery operation. Every 2 s for low battery / Polarity. Every 0,5 s for overcharge. Continuous for fault.
Failure Display LCD
Other Functions
Cold Start (Start-Up From Batteries) Yes
Emergency Stop (EPO) Yes
General
Operating Temperature 0° C ÷ 40° C
Relative Humidity Up to 95%, non-condensing
Maximum Operating Altitude 2,400 masl
Acoustic Noise At 1 Metre <50 dB (2)
Standards
Safety EN-IEC 62040-1
Electromagnetic Compatibility (EMC) EN 62040-2
Operation EN 62040-3
Quality And Environmental Management ISO 9001 & ISO 14001
Dimensions
Depth (Mm) 416
Width (Mm) 196
Height (Mm) 342
Weight
Weight (Kg) 22.16

Additional information

Weight 10 kg
The personable computer people