| Technical Specifications | |
|---|---|
| Technology | Line-interactive |
| Format | Tower |
| Input | |
| Rated Voltage | 230 V |
| Voltage Range 100% Load | 165 ÷ 290 V |
| Stabiliser | AVR (Buck & Boost) |
| Rated Frequency | 50 / 60 Hz (auto-detection) |
| Frequency Range | ±5 Hz |
| Auto~Detection Of Frequency | Yes |
| Protection | Resettable breaker |
| Output | |
| Rated Voltage | 230 V |
| Voltage Accuracy (Battery Mode) | ±10% |
| Power (Va/W) | 3000 / 2700 |
| Total Harmonic Distortion (THDV) | <5% |
| Waveform (Battery Mode) | Pure sine wave |
| Frequency | 50/60 Hz (same as input) |
| Frequency Accuracy (Battery Mode) | ±1 Hz |
| Compatibility With Apfc Loads | Yes (1) |
| Performance Stabiliser Mode (Avr) | >92% |
| Performance Battery Mode | |
| >80% | Admissible overloads in battery mode |
| 110% For 1 Min / >130% Immediate | Admissible overloads in-line mode |
| 110% 1Min / 120% Immediate | Socket type |
| IEC C13 + Terminals | |
| No. Of Sockets | 4 |
| Battery | |
| Battery Type | Pb-Ca sealed, AGM, maintenance-free |
| Charge Type | I/U (constant current/constant voltage) |
| Recharge Time | 4 hours to 90% |
| Battery Test | Automatic on each start-up + manual |
| Communication | |
| Ports | RS-232 / USB (HID) |
| Intelligent Slot | Slot for SNMP/potential-free contacts/ MODBUS |
| Monitoring Software | For Windows, Linux and Mac |
| Indications | |
| Type | LCD + keypad |
| Values | Input and output voltage / % load / % battery / backup |
| Levels | Connected load / overload / battery / low battery |
| Operating Modes | Normal / Stabilisation (AVR) / Battery / Fault |
| Alarm | Battery / low battery / overload / failure |
| Audible | Every 30 s for battery operation. Every 2 s for low battery / Polarity. Every 0,5 s for overcharge. Continuous for fault. |
| Failure | Display LCD |
| Other Functions | |
| Cold Start (Start-Up From Batteries) | Yes |
| Emergency Stop (EPO) | Yes |
| General | |
| Operating Temperature | 0° C ÷ 40° C |
| Relative Humidity | Up to 95%, non-condensing |
| Maximum Operating Altitude | 2,400 masl |
| Acoustic Noise At 1 Metre | <50 dB (2) |
| Standards | |
| Safety | EN-IEC 62040-1 |
| Electromagnetic Compatibility (EMC) | EN 62040-2 |
| Operation | EN 62040-3 |
| Quality And Environmental Management | ISO 9001 & ISO 14001 |
| Dimensions | |
| Depth (Mm) | 416 |
| Width (Mm) | 196 |
| Height (Mm) | 342 |
| Weight | |
| Weight (Kg) | 22.16 |